Free Online Developer Tool

Voltage Drop Calculator

Estimate voltage drop in DC, single-phase, and three-phase circuits. Calculate voltage loss, percentage drop, and load voltage using conductor size, cable length, current, and material.

DC & AC Circuits Copper & Aluminum Metric & AWG Sizes Voltage Drop %

Estimate cable voltage drop, percentage loss, and voltage at the load.

Circuit settings
Resistance-only AC estimate.
Resistance is adjusted from 20°C.
Voltage drop target

Results update as you change the inputs.

Voltage drop — Estimated conductor loss
Percentage drop — Relative to supply voltage
Voltage at load — Supply voltage minus estimated drop
Estimated conductor resistance — At the selected temperature
Voltage drop assessment

Enter your circuit details to see the estimate.

Calculation details

Length used —
Selected conductor area —
Temperature-adjusted resistivity —
Formula —

Estimate only. This tool uses a resistance-based approximation and does not verify cable ampacity, installation method, protective-device coordination, or compliance with local electrical codes. Consult a qualified electrical professional for design decisions.

How to Calculate Voltage Drop

A voltage drop calculator estimates how much voltage is lost as current flows through a cable. The amount depends on the conductor material, cross-sectional area, cable length, current, temperature, and circuit configuration.

How to Use This Calculator

  1. Select DC, AC single-phase, or AC three-phase.
  2. Choose copper or aluminum as the conductor material.
  3. Enter the supply voltage and load current.
  4. Enter the one-way cable length and select meters or feet.
  5. Select the conductor cross-section. Metric sizes and common AWG sizes are available.
  6. For AC circuits, enter the power factor. For DC, this field is not used.
  7. Enter the estimated conductor temperature and select an optional voltage-drop comparison target.

Voltage Drop Formula

This calculator uses a simplified resistance-based model. First, it estimates the resistance of one conductor using its material resistivity, length, and cross-sectional area. It then applies a circuit multiplier to estimate the voltage drop.

Conductor resistance:

R = ρ × L / A

  • R: Estimated resistance of one conductor, in ohms (Ω).
  • ρ: Temperature-adjusted resistivity, in Ω·mm²/m.
  • L: One-way cable length, in meters.
  • A: Conductor cross-sectional area, in mm².

DC and single-phase AC:

Voltage drop ≈ 2 × I × R for DC, and Voltage drop ≈ 2 × I × R × cos φ for the simplified single-phase AC estimate.

Balanced three-phase AC:

Voltage drop ≈ √3 × I × R × cos φ

Percentage voltage drop:

Voltage drop (%) = Voltage drop (V) / Supply voltage (V) × 100

Estimated load voltage:

Load voltage ≈ Supply voltage − Voltage drop

How Conductor Temperature Affects Resistance

Conductor resistance generally increases as its temperature rises. This calculator adjusts the nominal resistivity from 20°C using a linear temperature coefficient: approximately 0.00393 per °C for copper and 0.00403 per °C for aluminum.

This is an approximation. Actual cable resistance depends on the conductor’s construction, operating conditions, and manufacturer data.

Worked Example

Consider a single-phase AC circuit with a 230 V supply, a 32 A load, a 40 m one-way cable length, a 6 mm² copper conductor, a conductor temperature of 70°C, and a power factor of 0.9.

Using the simplified resistance model, the estimated voltage drop is approximately 7.9 V, or about 3.44% of the supply voltage. The estimated voltage at the load is approximately 222.1 V.

This example is an estimate, not a cable-sizing recommendation or a declaration of compliance with an electrical standard.

What Does the Voltage Drop Percentage Mean?

The percentage expresses the estimated voltage loss relative to the entered supply voltage. A comparison target such as 3% or 5% can help you review an estimate, but acceptable limits depend on the applicable electrical code, circuit type, equipment, and installation conditions. The selected target is not a compliance test.

Important Limitations

  • The model uses conductor resistance and does not include cable reactance, so it may not accurately represent every AC circuit, especially long runs or larger conductors.
  • The power-factor input is used as a simplified AC correction; it does not replace a full impedance calculation using resistance and reactance.
  • The calculation does not verify current-carrying capacity, insulation rating, installation method, grouping, ambient temperature correction factors, short-circuit protection, or terminal limits.
  • Actual conductor resistance may differ from the calculated value. Use manufacturer data and the applicable electrical standards for detailed design.
  • A calculated voltage drop below a selected target does not prove that a cable or installation is safe or code-compliant.

Use this calculator for preliminary estimates and learning. Have cable selection and electrical installation decisions verified by a qualified professional.

Frequently Asked Questions

What is voltage drop?

Voltage drop is the reduction in electrical voltage as current flows through a conductor. It depends on factors such as conductor resistance, current, cable length, and circuit configuration.

How do I calculate voltage drop percentage?

Divide the estimated voltage drop in volts by the supply voltage in volts, then multiply by 100. For example, a 6 V drop on a 230 V supply is approximately 2.61%.

Should I enter the one-way cable length or the total wire length?

Enter the one-way distance from the supply to the load. The calculation applies a factor of 2 for DC and single-phase circuits to account for the outgoing and return conductors. Three-phase circuits use a different multiplier.

Does this calculator support copper and aluminum cables?

Yes. Select the conductor material to use the corresponding nominal resistivity and temperature coefficient in the estimate.

Why does conductor temperature affect voltage drop?

Conductor resistance generally increases with temperature. Higher resistance produces a greater voltage drop for the same current and cable length. This calculator uses a linear temperature correction as an approximation.

Does the calculator include power factor?

For AC circuits, the entered power factor is applied in a simplified resistance-based formula. Cable reactance is not included, so this is not a complete AC impedance calculation. Power factor is not used for DC calculations.

Is a voltage drop below 3% always acceptable?

No. The appropriate limit depends on the circuit, equipment, applicable standards, and installation conditions. The 3% and 5% options are comparison targets only and do not establish compliance.

Does a low voltage drop mean the cable is safe to use?

No. Voltage drop is only one part of cable selection. Current-carrying capacity, insulation, installation method, ambient temperature, protection, and other requirements must also be checked.